Div. B › Part 11 › 11.4 › 11.4.2 — Reduction in Performance Level

11.4.2.3 — Change of Major Occupancy

Copied!
(1) Except as provided in Sentence 11.4.2.5. (4), the performance level of an existing building is reduced where proposed construction will result in,
(a) the change of the major occupancy of all or part of an existing building to another major occupancy of a greater hazard index,
(b) the conversion of a suite of a Group C major occupancy into more than one suite of Group C major occupancy,
(c) the conversion of a suite or part of a suite of a Group A, Division 2 or a Group A, Division 4 major occupancy into a gaming premises,
(d) the change of a farm building or part of a farm building to a major occupancy,
(e) the change of a building or part of a building to a post-disaster building,
(f) the change of a building or part of a building to a retirement home, or
(g) the change in use of a building or part of a building where the previous major occupancy of the building or part of the building cannot be determined.
(2) For the purpose of this Article and Sentences 11.4.2.1. (1) and 11.4.2.5. (4), the change of use set out in Clauses (1) (b) to (g) is also deemed to constitute a change in major occupancy.
(3) The performance level of an existing building is reduced where the early warning and evacuation systems requirements of other Parts for the proposed major occupancy exceed those of the existing building.
(4) The performance level of an existing building is reduced where the proposed major occupancy in the building is not separated from the adjoining major occupancies by fire separations having fire-resistance ratings conforming to Tables 3.1.3.1. and 11.4.3.4.B.
(5) The performance level of an existing building is reduced where the occupancy of all or part of an existing building of combustible construction is changed to a new major occupancy that would require the building, if it were a new building, to be of noncombustible construction or to be constructed in accordance with Article 3.2.2.43A. or 3.2.2.50A.
(6) Despite Clause (1) (a), the performance level of an existing building is reduced where proposed construction will result in the change of the major occupancy of all or part of an existing building to a Group C major occupancy in a building over 3 storeys in building height, except in a building conforming to Subclause 3.2.2.44. (1) (a) (ii) and having an egress facility conforming to Sentence 3.3.4.4. (8).
Tables & Figures referenced
Table 3.1.3.1 : Major Occupancy Fire Separations(1) : Forming Part of Sentence 3.1.3.1.(1)
Loading Table 3.1.3.1…
Table 11.4.3.4.B.(1) : Additional Upgrading for Multiple Major Occupancies : Forming Part of Sentences 11.4.2.3.(4) and 11.4.3.4.(4)
Loading Table 11.4.3.4.B…
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.