Div. B › Part 5 › 5.10 › 5.10.2 — Windows, Doors and Skylights

5.10.2.4 — Heat Transfer

Copied!
(1) Windows, doors and skylights shall meet the heat transfer performance requirements in Section 5.3.
(2) Except as provided in Sentence (3), all metal-framed glazed assemblies separating interior conditioned space from interior unconditioned space or exterior space shall incorporate a thermal break to minimize condensation.
(3) Metal-framed glazed assemblies need not comply with Sentence (2) where these assemblies are,
(a) storm windows or doors, or
(b) windows or doors that are required to have a fire-protection rating.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.