(1) Other fenestration assemblies and their components shall be designed and constructed in accordance with Section 5.6.
(2) Except as provided in Sentence (4), other fenestration assemblies and their components shall resist water penetration when tested in accordance with,
(a) ASTM E331, “Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by Uniform Static Air Pressure Difference”, or
(b) ASTM E547, “Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by Cyclic Static Air Pressure Difference”.
(3) Testing described in Sentence (2) shall be carried out at the driving rain wind pressure as calculated in accordance with CSA A440S1, “Canadian Supplement to AAMA/WDMA/CSA 101/I.S.2/A440-11, NAFS - North American Fenestration Standard/Specification for Windows, Doors, and Skylights”.
(4) The following need not comply with Sentence (2):
(a) interior windows and interior doors,
(b) vehicular access doors, including garage doors,
(c) storm windows and storm doors,
(d) commercial entrance systems,
(e) revolving doors,
(f) smoke and relief air vents,
(g) site-built door systems, and
(h) commercial steel doors.