Div. B › Part 5 › 5.10 › 5.10.4 — Other Fenestration Assemblies

5.10.4.3 — Heat Transfer

Copied!
(1) Other fenestration assemblies and their components shall meet the heat transfer performance requirements set out in Section 5.3.
(2) Other fenestration assemblies that are metal-framed and separate interior conditioned space from interior unconditioned space or exterior space shall incorporate a thermal break to minimize condensation.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.