Div. B › Part 6 › 6.2 › 6.2.11 — Storage Bins

6.2.11.1 — Storage Bins

Copied!
(1) Service pipes passing through a storage bin for solid fuel shall be protected or so located as to avoid damage to the pipes.
(2) Except for fuel-thawing pipes, every pipe designed to operate at a temperature of 50°C or above shall be located where fuel cannot be stored in contact with it.
(3) A storage bin for solid fuel shall not be located above a sewer opening or drain opening.
(4) Storage bins for solid fuel shall be designed and constructed so that the air temperature in the bin or the surface temperature of any part of the floor or walls is below 50°C.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.