(1) Dehumidifying cooling coil assemblies and condensate-producing heat exchangers shall be equipped with drain pans beneath them that are,
(a) designed in accordance with Section 5.11, Drain Pans, of ANSI/ASHRAE 62.1, “Ventilation for Acceptable Indoor Air Quality”,
(b) provided with an outlet that is piped to the outside of the airstream in a location where condensate can be eliminated,
(c) installed so that water drains freely from the pan, and
(d) provided with a drain line that is indirectly connected to a drainage system in accordance with Article 7.4.2.1.