Div. B › Part 6 › 6.2 › 6.2.3 — Air Duct Systems

6.2.3.5 — Underground Ducts

Copied!
(1) Underground ducts shall,
(a) be constructed and installed with a slope to provide interior drainage to all low points,
(b) not be connected directly to a sewer, and
(c) be installed and constructed of materials in conformance with ASHRAE Handbooks, SMACNA Manuals and the HRAI Digest.
(2) A clean-out or pump-out connection shall be provided in an underground duct system at every low point of the duct system.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.