(1) Except as provided in Sentence (3), all buildings shall be ventilated in accordance with this Part.
(2) Except in storage garages and repair garages covered by Article 6.2.2.3., the rates at which outdoor air is supplied in buildings by ventilation systems shall be not less than the rates required by ANSI/ASHRAE 62.1, “Ventilation for Acceptable Indoor Air Quality”.
(3) Self-contained mechanical ventilation systems serving a house or an individual dwelling unit shall conform to,
(a) this Part, or
(b) Subsection 9.32.3.
(4) Live/work units shall be mechanically ventilated in accordance with the requirements of Sentence (1).