(1) This Article applies to a mechanical ventilation system serving a house or an individual dwelling unit that contains a forced air heating system which is used for delivery of ventilation air.
(2) Where a mechanical ventilation system serves a Type I dwelling unit, a ventilation supply inlet is not required.
(3) Where a mechanical ventilation system serves a Type II dwelling unit, the system shall include a heat recovery ventilator, coupled to the forced air heating system, installed in accordance with Article 9.32.3.11.
(4) The forced air heating system circulation fan shall be controlled by a manual switch located adjacent to the ventilation fan switch required in Sentence 9.32.3.4. (4).
(5) The switch required in Sentence (4) shall be identified by the words CIRCULATION FAN.