9.32.3.6 — Ventilation Systems Coupled with Forced Air Heating Systems

Copied!
(1) This Article applies to a mechanical ventilation system serving a house or an individual dwelling unit that contains a forced air heating system which is used for delivery of ventilation air.
(2) Where a mechanical ventilation system serves a Type I dwelling unit, a ventilation supply inlet is not required.
(3) Where a mechanical ventilation system serves a Type II dwelling unit, the system shall include a heat recovery ventilator, coupled to the forced air heating system, installed in accordance with Article 9.32.3.11.
(4) The forced air heating system circulation fan shall be controlled by a manual switch located adjacent to the ventilation fan switch required in Sentence 9.32.3.4. (4).
(5) The switch required in Sentence (4) shall be identified by the words CIRCULATION FAN.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.