(1) Fire stop flaps in ceiling membranes referred to in Sentence 9.10.5.1. (4) shall,
(a) conform to CAN/ULC-S112.2, “Fire Test of Ceiling Firestop Flap Assemblies”, and
(b) activate at a temperature approximately 30°C above the normal maximum temperature that occurs in the ducts, whether the air duct system is operating or shut down.