Div. B › Part 9 › 9.10 › 9.10.13 — Doors, Dampers and Other Closures in Fire Separations

9.10.13.14 — Fire Stop Flaps

Copied!
(1) Fire stop flaps in ceiling membranes referred to in Sentence 9.10.5.1. (4) shall,
(a) conform to CAN/ULC-S112.2, “Fire Test of Ceiling Firestop Flap Assemblies”, and
(b) activate at a temperature approximately 30°C above the normal maximum temperature that occurs in the ducts, whether the air duct system is operating or shut down.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.