Div. B › Part 9 › 9.9 › 9.9.2 — Types and Purpose of Exits

9.9.2.3 — Elevators, Slide Escapes and Windows as Means of Egress

Copied!
(1) Elevators, slide escapes or windows shall not be considered as part of a required means of egress.
(2) Except for floor areas of mercantile occupancy, casement windows not less than 1 060 mm high, 560 mm wide, with a sill height not more than 900 mm above the inside floor, are permitted to be considered part of a required means of egress to provide access to fire escapes, when fire escapes are permitted.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.