Div. B › Part 9 › 9.21 › 9.21.1 — General

9.21.1.1 — Application

Copied!
(1) This Section applies to,
(a) rectangular masonry or concrete chimneys not more than 12 m in height serving fireplaces or serving appliances having a combined total rated heat output of 120 kW or less, and
(b) flue pipes serving solid fuel-burning appliances.
(2) Except as provided in Sentence 9.21.1.3. (1), chimneys (other than those described in Sentence (1) and Sentence 9.21.1.2. (1)), gas vents and flue pipes serving gas-, oil- or solid fuel-burning appliances and associated equipment shall conform to Section 6.3.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.