Div. B › Part 9 › 9.9 › 9.9.12 — Lighting

9.9.12.2 — Required Lighting in Egress Facilities

Copied!
(1) Every exit, public corridor or corridor providing access to exit for the public shall be equipped to provide illumination to an average level of not less than 50 lx at floor or tread level and at all points such as angles and intersections at changes of level where there are stairs or ramps.
(2) The minimum value of the illumination required by Sentence (1) shall be not less than 10 1x.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.