9.20.8.2 — Cavity Walls Supporting Framing Members

Copied!
(1) Floor joists supported on cavity walls shall be supported on solid masonry units not less than 57 mm high.
(2) Floor joists described in Sentence (1) shall not project into the cavity.
(3) Roof and ceiling framing members bearing on cavity walls shall be supported on,
(a) solid masonry units not less than 57 mm high, bridging the full thickness of the wall, or
(b) a wood plate not less than 38 mm thick, bearing not less than 50 mm on each wythe.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.