Div. B › Part 9 › 9.23 › 9.23.4 — Maximum Spans

9.23.4.4 — Concrete Topping

Copied!
(1) Except as permitted in Sentence (2), where a floor is required to support a concrete topping, the joist spans shown in Table A-1 or the spacing of the members shall be reduced to allow for the loads due to the topping.
(2) Where a floor is required to support a concrete topping, joist spans are permitted to be selected from Table A-2 provided the concrete,
(a) is 38 to 51 mm thick,
(b) is normal weight,
(c) is placed directly on the subflooring, and
(d) has not less than 20 MPa compressive strength after 28 days.
(3) Where a floor is required to support a concrete topping not more than 51 mm thick, the beam spans shown in Tables A-8 to A-11 shall be multiplied by 0.8 or the supported length of the floor joists shall be reduced to allow for the loads due to the topping.
Tables & Figures referenced
Table A-1 : Maximum Spans for Floor Joists – General Cases(1) : Forming Part of Sentence 9.23.4.2.(1)
Loading Table A-1…
Table A-2 : Maximum Spans for Floor Joists – Special Cases(1) : Forming Part of Sentence s 9.23.4.2.(1) and 9.23.4.4.(2)
Loading Table A-2…
Table A-8 : Maximum Spans for Built-up Floor Beams Supporting not more than One Floor(1)(2) : Forming Part of Sentence 9.23.4.2.(3)
Loading Table A-8…
Table A-11 : Maximum Spans for Glue-Laminated Floor Beams – 20f-E Grade(1) : Forming Part of Sentence 9.23.4.2.(3)
Loading Table A-11…
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.