Div. B › Part 9 › 9.9 › 9.9.7 — Access to Exits

9.9.7.3 — Dead-End Corridors

Copied!
(1) A dead-end public corridor is permitted in an occupancy shown in Table 9.9.7.3., where,
(a) the dead-end corridor,
(i) does not exceed the distance of travel measured from the most remote point of the dead-end to a point where it is possible to go in opposite directions to each of two separate exits, and
(ii) is provided with doors equipped with self-closing devices, or
(b) there is a second and separate egress doorway from each room or suite not leading into the dead-end corridor.
(2) Dead-end public corridors in residential occupancies and business and personal services occupancies shall contain only suite door openings arranged so that not more than two such doors have to be passed to reach the nearest exit.
(3) The area of wired glass in doors required by Sentence (2) shall not exceed 645 cm².
Tables & Figures referenced
Table 9.9.7.3 : Dead-End Public Corridors : Forming Part of Sentence 9.9.7.3.(1)
Loading Table 9.9.7.3…
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.