Div. B › Part 9 › 9.21 › 9.21.4 — Masonry and Concrete Chimney Construction

9.21.4.5 — Lateral Stability

Copied!
(1) Except as provided in Sentence (2), chimneys shall be braced in accordance with Subsection 4.3.2. to provide stability under wind loads.
(2) A chimney need not be laterally braced provided,
(a) no horizontal outside dimension is less than 400 mm, and
(b) the chimney extends not more than 3.6 m above a roof or the masonry wall of which it forms a part.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.