Div. B › Part 9 › 9.20 › 9.20.1 — Application

9.20.1.1 — General

Copied!
(1) Except as provided in Article 9.20.1.2., this Section applies to,
(a) unreinforced masonry and masonry veneer walls not in contact with the ground, where,
(i) the height of the walls constructed on the foundation walls does not exceed 11 m, and
(ii) the roof or floor assembly above the first storey is not of concrete construction, and
(b) flat insulating concrete form walls not in contact with the ground that,
(i) have a maximum floor to floor height of 3 m,
(ii) are erected in houses not more than 2 storeys in building height, and
(iii) are erected in locations where the seismic spectral response acceleration, Sa(0.2), is not greater than 0.4.
(2) For walls other than those described in Sentence (1), or where the masonry walls or insulating concrete form walls not in contact with the ground are designed for specified loads on the basis of ultimate and serviceability limit states, Subsection 4.3.2. shall apply.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.