(1) Except as provided in Sentence (2), a dwelling unit and a suite in hotels shall be separated from every other space in a building in which noise may be generated by,
(a) a separating assembly and adjoining construction, which, together, provide an apparent sound transmission class rating of not less than 47, or
(b) a separating assembly that provides a sound transmission class rating of at least 50 and adjoining construction that conforms to Article 9.11.1.4.
(2) Construction separating a dwelling unit or suite in a hotel from an elevator shaft or refuse chute shall have an STC rating of at least 55.