9.10.8.2 — Fire-Resistance Ratings in Sprinklered Buildings

Copied!
(1) Except for roofs that support an occupancy, the requirements in Table 9.10.8.1. for roof assemblies to have a fire-resistance rating are permitted to be waived in sprinklered buildings where,
(a) the sprinkler system is electrically supervised in conformance with Sentence 3.2.4.10. (3), and
(b) the operation of the sprinkler system will cause a signal to be transmitted to the fire department in conformance with Sentence 3.2.4.8. (4).
Tables & Figures referenced
Table 9.10.8.1 : Fire Resistance Ratings for Structural Members and Assemblies : Forming Part of Sentence 9.10.8.1.(1)
Loading Table 9.10.8.1…
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.