Div. B › Part 9 › 9.10 › 9.10.18 — Alarm and Detection Systems

9.10.18.2 — Fire Alarm System Required

Copied!
(1) Except as provided in Sentence (2), a fire alarm system shall be installed,
(a) in every building that contains more than 3 storeys, including storeys below the first storey,
(b) where the total occupant load exceeds 300, or
(c) when the occupant load for any major occupancy in Table 9.10.18.2. is exceeded.
(2) A fire alarm system is not required in a residential occupancy where an exit or public corridor serves not more than 4 suites or where each suite has direct access to an exterior exit facility leading to ground level.
Tables & Figures referenced
Table 9.10.18.2 : Maximum Occupant Load for Buildings without Fire Alarm Systems : Forming Part of Sentence 9.10.18.2.(1)
Loading Table 9.10.18.2…
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.