9.23.3.5 — Fastening for Sheathing or Subflooring

Copied!
(1) Except as required by Sentence (5), fastening of sheathing and subflooring shall conform to Table 9.23.3.5.
(2) Staples shall not be less than 1.6 mm in diameter or thickness, with not less than a 9.5 mm crown driven with the crown parallel to framing.
(3) Roofing nails for the attachment of fibreboard or gypsum sheathing shall not be less than 3.2 mm in diameter with a minimum head diameter of 11.1 mm.
(4) Flooring screws shall not be less than 3.2 mm in diameter.
(5) Where roof sheathing supports are spaced at more than 406 mm o.c., the maximum spacing of fasteners for roof sheathing shall be 150 mm along edges and intermediate supports.
Tables & Figures referenced
Table 9.23.3.5 : Fasteners for Sheathing and Subflooring : Forming Part of Sentence 9.23.3.5.(1)
Loading Table 9.23.3.5…
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.