Div. B › Part 9 › 9.13 › 9.13.2 — Dampproofing

9.13.2.6 — Dampproofing of Floors-on-Ground

Copied!
(1) Where dampproofing is installed below the floor, it shall consist of,
(a) polyethylene not less than 0.15 mm thick with joints lapped not less than 100 mm,
(b) Type S roll roofing with joints lapped not less than 100 mm, or
(c) rigid extruded/expanded polystyrene with sealed or ship-lapped joints that has,
(i) sufficient compressive strength to support the floor assembly, and
(ii) a water vapour permeance complying with Clause 9.13.2.2. (2) (b).
(2) Where dampproofing is installed between a floor-on-ground and a finished floor, it shall consist of,
(a) rigid extruded/expanded polystyrene with sealed or ship-lapped joints that has,
(i) sufficient compressive strength to support the floor assembly, and
(ii) a water vapour permeance complying with Clause 9.13.2.2. (2) (b), or
(b) polyethylene not less than 0.05 mm with joints lapped not less than 100 mm.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.