Div. B › Part 9 › 9.18 › 9.18.7 — Fire Protection

9.18.7.1 — Crawl Spaces as Warm Air Plenums

Copied!
(1) Only crawl spaces under 1-storey portions of dwelling units shall be used as warm air plenums.
(2) Enclosing material in crawl spaces described in Sentence (1), including insulation, shall have a surface flame-spread rating not greater than 150.
(3) Combustible ground cover used as enclosing material in Sentence (2) shall be covered with noncombustible material.
(4) Noncombustible material described in Sentence (3) shall,
(a) extend not less than 300 mm beyond the projection of a register opening, and
(b) have turned-up edges.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.