Div. B › Part 9 › 9.21 › 9.21.5 — Clearance from Combustible Construction

9.21.5.1 — Clearance from Combustible Materials

Copied!
(1) The clearance between masonry or concrete chimneys and combustible framing material shall be not less than,
(a) 50 mm for interior chimneys, and
(b) 12 mm for exterior chimneys.
(2) A clearance of not less than 150 mm shall be provided between a cleanout opening and combustible material.
(3) Combustible flooring, subflooring and ceiling finishes shall have not less than a 12 mm clearance from masonry or concrete chimneys.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.