Div. B › Part 9 › 9.9 › 9.9.4 — Fire Protection of Exits

9.9.4.7 — Stairways in Group D or E Buildings

Copied!
(1) Notwithstanding the requirements of Sentences 9.9.4.2. (1), 9.9.8.2. (1) and Article 9.10.9.5., where a suite of Group D or E occupancy is located partly on the first storey and partly on the second storey or partly on the second storey and partly on the third storey, stairways serving that suite need not be constructed as exit stairs, provided,
(a) the building is not greater than three storeys in building height,
(b) the suite is separated from other occupancies by a fire separation having a fire-resistance rating of not less than 45 min,
(c) the area occupied by the suite is not greater than 100 m² per storey, other than the exit level storey,
(d) the maximum travel distance from any point in the suite to an exterior exit is not greater than 25 m,
(e) the floor assemblies have a fire-resistance rating of not less than 45 min or are of noncombustible construction,
(f) the basement and first storey are separated by a fire separation having a fire-resistance rating of not less than 45 min, and
(g) a smoke alarm is installed on each floor of the suite, including the basement, in accordance with Subsection 9.10.19. (2) Revoked: O. Reg. 191/14, s. 99.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.