(1) Continuous perimeter foundation walls are not required, but when they are provided, they shall comply with the requirements of this Part.
(2) Where unit masonry columns are used, the height of such columns shall not exceed,
(a) in the case of hollow masonry units, 4 times the least dimension of the units,
(b) in the case of solid masonry units or hollow units with voids filled with concrete, 10 times the least dimension of the column, or
(c) where the column is reinforced with at least four 13 mm diam bars and filled with concrete, 18 times the least dimension of the column.
(3) Columns in excess of the height limitations of Clauses (2) (a) to (c) shall be designed in accordance with Part 4.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.