Div. B › Part 9 › 9.10 › 9.10.13 — Doors, Dampers and Other Closures in Fire Separations

9.10.13.1 — Closures

Copied!
(1) Except as provided in Article 9.10.13.2., openings in required fire separations shall be protected with a closure conforming to Table 9.10.13.1. and shall be installed in conformance with NFPA 80, “Fire Doors and Other Opening Protectives”, unless otherwise specified in this Part.
Tables & Figures referenced
Table 9.10.13.1 : Fire-Protection Ratings for Closures : Forming Part of Sentence 9.10.13.1.(1)
Loading Table 9.10.13.1…
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.