Div. B › Part 9 › 9.23 › 9.23.4 — Maximum Spans

9.23.4.3 — Steel Beams

Copied!
(1) The spans for steel beams with laterally supported top flanges shall conform to Table 9.23.4.3. for floors and Tables A-20 to A-29 for roofs and floors.
(2) Beams described in Sentence (1) shall at least meet the requirements for Grade 350 W steel in CSA G40.21, “Structural Quality Steel”.
(3) A beam may be considered to be laterally supported if,
(a) the wood joists bear on its top flange at intervals of 610 mm or less over its entire length,
(b) the load being applied to this beam is transmitted through the joists, and
(c) 19 mm by 38 mm wood strips in contact with the top flange are nailed on both sides of the beam to the bottom of the joist supported.
Tables & Figures referenced
Table A-20 : Maximum Spans for Steel Beams Supporting a Roof and One Floor in Dwelling Units Where Beams Support Exterior Stud Walls with Brick Veneer – 1.0 kPa Specified Roof Snow Load : Forming Part of Sentence 9.23.4.3.(1)
Loading Table A-20…
Table A-29 : Maximum Spans for Steel Beams Supporting a Roof and One Floor in Dwelling Units Where Beams Support Interior Stud Walls or Exterior Stud Walls with Siding – 3.0 kPa Specified Roof Snow Load : Forming Part of Sentence 9.23.4.3.(1)
Loading Table A-29…
Table 9.23.4.3 : Maximum Spans for Steel Beams Supporting Floors in Dwelling Units : Forming Part of Sentence 9.23.4.3.(1)
Loading Table 9.23.4.3…
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.