Div. B › Part 9 › 9.8 › 9.8.8 — Guards

9.8.8.2 — Loads on Guards

Copied!
(1) Except as provided in Sentences (2), (4) and (5), guards shall be designed to resist the specified loads prescribed in Table 9.8.8.2.
(2) For guards within dwelling units and in exterior guards serving not more than 2 dwelling units, where the width and spacing of pickets are such that three pickets can be engaged by a load imposed over a 300 mm width, the load shall be imposed so as to engage three pickets.
(3) None of the specified loads prescribed in Table 9.8.8.2. need be considered to act simultaneously.
(4) For guards within dwelling units and for exterior guards serving not more than 2 dwelling units, Table 9.8.8.2. need not apply where the guard construction has been demonstrated to provide effective performance.
(5) Guards constructed in accordance with the requirements in MMAH Supplementary Standard SB-7, “Guards for Housing and Small Buildings” shall be deemed to satisfy the requirements of Sentence (1).
Tables & Figures referenced
Table 9.8.8.2 : Specified Loads for Guards : Forming Part of Sentence 9.8.8.2.(1)
Loading Table 9.8.8.2…
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.