Div. B › Part 9 › 9.9 › 9.9.2 — Types and Purpose of Exits

9.9.2.1 — Types of Exits

Copied!
(1) Except as otherwise provided in this Section, an exit from any floor area shall be one of the following used singly or in combination:
(a) an exterior doorway,
(b) an exterior passageway,
(c) an exterior ramp,
(d) an exterior stairway,
(e) a fire escape (as described in Subsection 3.4.7.),
(f) a horizontal exit,
(g) an interior passageway,
(h) an interior ramp, or
(i ) an interior stairway.
(2) Fire escapes are permitted to be used as exits on existing buildings provided they are designed and installed in conformance with Subsection 3.4.7.
(3) Fire escapes shall not be installed on any new building.
(4) Where a horizontal exit is used, it shall conform to Sentence 3.4.1.6. (1) and Article 3.4.6.10.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.