Div. B › Part 9 › 9.20 › 9.20.13 — Control of Rain Water Penetration

9.20.13.8 — Required Weep Holes

Copied!
(1) Weep holes spaced not more than 800 mm apart shall be provided at the bottom of,
(a) cavities in cavity walls, and
(b) cavities or air spaces in masonry veneer walls.
(2) The cavities or air spaces described in Sentence (1) shall include those above lintels over window and door openings required to be flashed in conformance with Article 9.20.13.3.
(3) The weep holes required in Sentence (1) shall be in a location such that any water that collects in the cavity or space will be directed to the exterior of the building.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.