Div. B › Part 9 › 9.27 › 9.27.3 — Second Plane of Protection

9.27.3.5 — Sheathing Membranes in Lieu of Sheathing

Copied!
(1) Except as provided in Article 9.27.3.6., where no sheathing is used, at least two layers of sheathing membrane shall be applied beneath the cladding.
(2) All joints in the sheathing membrane required in Sentence (1) shall occur over framing, and the membrane shall be fastened to the framing with roofing nails or staples spaced not more than 150 mm along the edges of the outer layer of sheathing paper.
(3) Wall sheathing is permitted to be used in lieu of one layer of sheathing membrane required in Sentence (1), and the thickness need not conform to Table 9.23.16.2.A.
Tables & Figures referenced
Table 9.23.16.2.A : Wall Sheathing Thickness and Specifications : Forming Part of Sentence 9.23.16.2.(1)
Loading Table 9.23.16.2.A…
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.