Div. B › Part 9 › 9.21 › 9.21.4 — Masonry and Concrete Chimney Construction

9.21.4.6 — Chimney Caps

Copied!
(1) The top of a chimney shall have a waterproof cap of reinforced concrete, masonry or metal.
(2) The cap required in Sentence (1) shall slope from the lining and be provided with a drip not less than 25 mm from the chimney wall.
(3) Cast-in-place concrete caps shall be separated from the chimney liner by a bond break and be sealed at that location.
(4) Jointed precast concrete or masonry chimney caps shall have flashing installed beneath the cap extending from the liner to the drip edge.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.