Div. B › Part 9 › 9.26 › 9.26.4 — Flashing at Intersections

9.26.4.8 — Chimney Saddles

Copied!
(1) Except as otherwise permitted in Sentence (5), chimney saddles shall be installed where the upper side of a chimney on a sloping roof is more than 750 mm wide.
(2) Chimney saddles shall be covered with sheet metal or roofing material of weight and quality equivalent to the roofing.
(3) Saddles shall be flashed where they intersect the roof.
(4) The intersection of the saddle and the chimney shall be flashed and counterflashed as required in Article 9.26.4.4.
(5) A chimney saddle need not be installed if the intersection between the chimney and roof is protected by sheet metal flashing that extends up the chimney to a height equal to at least one-sixth the width of the chimney, but not less than 150 mm, and up the roof slope to a point equal in height to the flashing on the chimney, but not less than 1.5 times the shingle exposure.
(6) Flashing described in Sentence (5) at the chimney shall be counterflashed as required by Article 9.26.4.4.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.