Div. B › Part 9 › 9.3 › 9.3.1 — Concrete

9.3.1.1 — General

Copied!
(1) Except as provided in Sentence (2) and Articles 9.3.1.6. and 9.3.1.7., unreinforced and nominally reinforced concrete shall be designed, mixed, placed, cured and tested in accordance with the requirements for “R” class concrete stated in Section 9 of CSA A23.1, “Concrete Materials and Methods of Concrete Construction”.
(2) Unreinforced and nominally reinforced site-batched concrete shall be designed, mixed, placed and cured in accordance with Articles 9.3.1.2. to 9.3.1.9.
(3) Except as provided in Sentence (4), Subsection 9.15.4. and Section 9.39., reinforced concrete shall be designed to conform to the requirements of Part 4.
(4) For flat insulating concrete form walls described in Clause 9.15.1.1. (1) (c) or 9.20.1.1. (1) (b), the concrete and reinforcing shall comply with Part 4 or,
(a) the concrete shall conform to CSA A23.1, “Concrete Materials and Methods of Concrete Construction”, with a maximum aggregate size of 19 mm, and
(b) the reinforcing shall,
(i) conform to CSA G30.18, “Carbon Steel Bars for Concrete Reinforcement”,
(ii) have a minimum specified yield strength of 400 MPa, and
(iii) be lapped a minimum of 450 mm for 10M bars and 650 mm for 15M bars.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.