Div. B › Part 9 › 9.20 › 9.20.17 — Above-Ground Flat Insulating Concrete Form Walls

9.20.17.4 — Openings in Loadbearing Flat Insulating Concrete Form Walls

Copied!
(1) No openings shall occur within 1.2 m of interior and exterior corners of exterior loadbearing flat insulating concrete form walls.
(2) In loadbearing flat insulating concrete form walls, lintels shall be provided over all openings wider than 900 mm.
(3) Lintels described in Sentence (2) shall be constructed in accordance with Tables A-17, A-18 or A-19.
(4) Lintels described in Sentence (2) over openings wider than 1.2 m shall be reinforced for shear with 10M stirrups at a maximum spacing of half the distance from the bottom reinforcing bar to the top of the lintel.
Tables & Figures referenced
Table A-17 : Maximum Allowable Clear Spans for Lintels in Flat Loadbearing Insulating Concrete Form (ICF) Walls(1)(2)(3) (1-10M Bottom Bar) : Forming Part of Sentence 9.20.17.4.(3)
Loading Table A-17…
Table A-18 : Maximum Allowable Clear Spans for Lintels in Flat Loadbearing Insulating Concrete Form (ICF) Walls(1)(2)(3) (1-15M Bottom Bar) : Forming Part of Sentence 9.20.17.4.(3)
Loading Table A-18…
Table A-19 : Maximum Allowable Clear Spans for Lintels in Flat Loadbearing Insulating Concrete Form (ICF) Walls(1)(2)(3) (2-15M Bottom Bar) : Forming Part of Sentence 9.20.17.4.(3)
Loading Table A-19…
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.