Div. B › Part 9 › 9.28 › 9.28.6 — Stucco Application

9.28.6.3 — First Coat

Copied!
(1) The first coat shall be not less than 6 mm thick, measured from the face of the lath or masonry, fully embedding the lath.
(2) The surface of the first coat shall be scored to provide a key with the second coat.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.