(1) Floor joists supported on the side of flat insulating concrete form walls shall be supported with joist hangers secured to wood ledger boards.
(2) The ledger boards described in Sentence (1) shall be not less than,
(a) 38 mm thick, and
(b) the depth of the floor joists.
(3) Anchor bolts shall be used to secure ledger boards to flat insulating concrete form walls and shall be,
(a) embedded in the wall to a depth not less than 100 mm, and
(b) spaced in accordance with Table 9.20.17.5.
(4) Floor joists and building frames supported on top of flat insulating concrete form walls shall be anchored in conformance with Article 9.23.6.1.
Tables & Figures referenced
Table 9.20.17.5 : Maximum Anchor Bolt Spacing for the Connection of Ledger Boards to Flat Insulating Concrete Form Walls : Forming Part of Sentence 9.20.17.5.(3)
Loading Table 9.20.17.5…
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.