Div. B › Part 9 › 9.10 › 9.10.15 — Spatial Separation Between Houses

9.10.15.5 — Construction of Exposing Building Face of Houses

Copied!
(1) Except as provided in Sentences (2) to (4) and (6), each exposing building face and any exterior wall located above an exposing building face that encloses an attic or roof space shall be constructed in conformance with Subsection 9.10.8.,
(a) for the exposing building face as a whole, or
(b) for any number of separate portions of the exposing building face.
(2) Sentence (1) does not apply where,
(a) the limiting distance is not less than 1.2 m,
(b) the limiting distance is less than 1.2 m but not less than 0.6 m, provided that the exposing building face has a fire-resistance rating of not less than 45 min, or
(c) the limiting distance is less than 0.6 m, provided that the exposing building face has a fire-resistance rating of not less than 45 min and is clad with noncombustible material.
(3) Where the limiting distance is less than 0.6 m, cladding on the exposing building face and on exterior walls located above the exposing building face that enclose an attic or roof spaces need not be noncombustible, provided the cladding,
(a) conforms to Subsection 9.27.12.,
(b) is installed without furring members over not less than 12.7 mm thick gypsum sheathing or over masonry,
(c) has a flame-spread rating not more than 25 when tested in accordance with Sentence 3.1.12.1. (2), and
(d) is not more than 2 mm in thickness exclusive of fasteners, joints and local reinforcements.
(4) The requirements for fire-resistance rating, type of construction and type of cladding need not apply to the exposing building faces of a house and a detached garage or accessory building that face each other, where,
(a) the detached garage or accessory building serves the house or an individual dwelling unit in the house,
(b) the detached garage or accessory building is located on the same property as the house, and
(c) the house is the only major occupancy on the property.
(5) Except for houses, combustible projections on the exterior of a wall that are more than 1 000 mm above ground level, such as balconies, platforms, canopies, eave projections and stairs, and that could expose an adjacent building to fire spread, shall not be permitted within,
(a) 1.2 m of a property line or the centre line of a public way, or
(b) 2.4 m of a combustible projection on another building on the same property.
(6) Heavy timber and steel columns need not conform to the requirements of Sentence (1) provided the limiting distance is not less than 3 m.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.