Div. B › Part 9 › 9.20 › 9.20.17 — Above-Ground Flat Insulating Concrete Form Walls

9.20.17.6 — Anchoring of Roof Framing to Top of Flat Insulating Concrete Form Walls

Copied!
(1) Roof framing supported on the top of flat insulating concrete form walls shall be fixed to the top plates, which shall be anchored to the wall with anchor bolts,
(a) not less than 12.7 mm in diameter, and
(b) spaced not more than 1.2 m o.c.
(2) The anchor bolts described in Sentence (1) shall be placed in the centre of the flat insulating concrete form wall and shall be embedded not less than 100 mm into the concrete.
(3) Attachment of roof framing to wood top plates shall be in accordance with Table 9.23.3.4.
Tables & Figures referenced
Table 9.23.3.4 : Nailing for Framing : Forming Part of Sentence 9.23.3.4.(1)
Loading Table 9.23.3.4…
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.