Div. B › Part 9 › 9.9 › 9.9.8 — Exits from Floor Areas

9.9.8.2 — Number of Required Exits

Copied!
(1) Except as provided in Sentences (2) and (3) and Subsection 9.9.9., at least two exits shall be provided from every floor area, spaced so that the travel distance to the nearest exit is not more than,
(a) 40 m in the case of business and personal services occupancies,
(b) 45 m for all occupancies where the floor area is sprinklered, and
(c) 30 m for all other occupancies.
(2) Except as provided in Subsection 9.9.9., a single exit is permitted from each storey in buildings of 1 and 2 storeys in building height provided the floor area and travel distance requirements conform to those required in Article 9.9.7.4. and the total occupant load served by an exit facility does not exceed 60 persons.
(3) In boarding, lodging or rooming houses,
(a) where sleeping accommodation is provided for not more than eight persons, a single exit is permitted from each floor area, or
(b) where sleeping accommodation is not provided in the basement, a single exit is permitted from the basement floor area.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.