Div. B › Part 9 › 9.8 › 9.8.4 — Step Dimensions

9.8.4.4 — Uniformity and Tolerances for Risers, Runs and Treads

Copied!
(1) Except as provided in Sentence (2), risers shall be of uniform height in any one flight with a maximum tolerance of,
(a) 5 mm between adjacent treads or landings, and
(b) 10 mm between the tallest and shortest risers in a flight.
(2) Except for required exit stairs, where the top or bottom riser in a stair adjoins a sloping finished walking surface such as a garage floor, driveway or sidewalk, the height of the riser across the stair shall vary by not more than 1 in 12.
(3) Rectangular treads shall have uniform run with a maximum tolerance of,
(a) 5 mm between adjacent treads, and
(b) 10 mm between the deepest and shallowest treads in a flight.
(4) Tapered treads in a flight shall have a uniform run in accordance with the tolerances described in Sentence (3) when measured at a point 300 mm from the centre line of the inside handrail.
(5) The slope of treads shall not exceed 1 in 50.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.