Div. B › Part 9 › 9.27 › 9.27.5 — Attachment of Cladding

9.27.5.7 — Penetration of Fasteners

Copied!
(1) Fasteners for shakes and shingles shall penetrate through the nail-holding base or not less than 19 mm into the framing.
(2) Fasteners for cladding other than that described in Sentence (1) shall penetrate through the nail-holding base or not less than 25 mm into the framing.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.