Div. B › Part 9 › 9.10 › 9.10.17 — Flame Spread Limits

9.10.17.1 — Flame-Spread Rating of Interior Surfaces

Copied!
(1) Except as otherwise provided in this Subsection, the exposed surface of every interior wall and ceiling, including skylights and glazing, shall have a surface flame-spread rating of not more than 150.
(2) Except as permitted in Sentence (3), doors need not conform to Sentence (1) provided they have a surface flame-spread rating of not more than 200.
(3) Doors within dwelling units, other than vehicle garage doors, need not conform to Sentences (1) and (2).
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.