Div. B › Part 9 › 9.10 › 9.10.9 — Fire Separations Between Rooms and Spaces Within Buildings

9.10.9.13 — Separation of Suites

Copied!
(1) Except as required in Article 9.10.9.14. and as permitted by Sentence (2), each suite in other than business and personal services occupancies shall be separated from adjoining suites by a fire separation having a fire-resistance rating of not less than 45 min.
(2) In sprinklered buildings, suites of business and personal services occupancy and mercantile occupancy that are served by public corridors conforming with Sentence 3.3.1.4. (4) are not required to be separated from each other by fire separations.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.