Div. B › Part 9 › 9.25 › 9.25.4 — Vapour Barriers

9.25.4.3 — Installation of Vapour Barriers

Copied!
(1) Products installed to function as the vapour barrier shall protect the warm side of wall, ceiling and floor assemblies.
(2) Where different products are used for the vapour barrier and the insulation, the vapour barrier shall be installed sufficiently close to the warm side of the insulation to prevent condensation at design conditions.
(3) Where the same product is used for the vapour barrier and the insulation, the product shall be installed sufficiently close to the warm side of the assembly to prevent condensation at design conditions.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.