Div. B › Part 9 › 9.10 › 9.10.19 — Smoke Alarms

9.10.19.1 — Required Smoke Alarms

Copied!
(1) Except as permitted in Article 9.10.19.8., smoke alarms conforming to CAN/ULC-S531, “Smoke Alarms”, shall be installed in,
(a) each dwelling unit,
(b) each sleeping room not within a dwelling unit, and
(c) each interior shared means of egress and common area in a house.
(2) Smoke alarms required in Sentence (1) shall have a visual signalling component conforming to the requirements in 18.5.3. (Light, Color and Pulse Characteristics) of NFPA 72, “National Fire Alarm and Signaling Code”.
(3) The visual signalling component required in Sentence (2) need not,
(a) be integrated with the smoke alarm provided it is interconnected to it,
(b) be on battery backup, or
(c) have synchronized flash rates, when installed in a house or an individual dwelling unit.
(4) The luminous intensity for visual signalling components required in Sentence (2) that are installed in sleeping rooms shall be a minimum of 175 cd.
(5) Smoke alarms required in Sentence (1) shall be installed on or near the ceiling.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.