Div. B › Part 9 › 9.25 › 9.25.3 — Air Barrier Systems

9.25.3.1 — Required Barrier to Air Leakage

Copied!
(1) Wall, ceiling and floor assemblies that separate conditioned spaces from unconditioned spaces or from the ground shall be constructed so as to include an air barrier system that will provide a continuous barrier to air leakage,
(a) from the interior of the building into wall, floor, attic or roof spaces sufficient to prevent excessive moisture condensation in such spaces during the heating season, and
(b) from the exterior inward sufficient to prevent moisture condensation on the room side during the heating season.
(2) The continuity of the air barrier system shall extend throughout the basement.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.