Div. B › Part 9 › 9.10 › 9.10.22 — Fire Protection for Gas, Propane and Electric Cooktops

9.10.22.2 — Vertical Clearances above Cooktops

Copied!
(1) Except as provided in Sentence (2), framing, finishes and cabinetry installed directly above the location of the cooktop shall be not less than 750 mm above the level of cooktop burners or elements.
(2) The vertical clearance described in Sentence (1) for framing, finishes and cabinets located directly above the location of the cooktop is permitted to be reduced to 600 mm above the level of the elements or burners provided the framing, finishes and cabinets,
(a) are noncombustible, or
(b) are protected by a metal hood with a 125 mm projection beyond the framing, finishes and cabinets.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.